Explore Products

My Quote Request

No products added yet

5925-01-317-9328

20 Products

HMCP015E0

CIRCUIT BREAKER

NSN, MFG P/N

5925013179328

NSN

5925-01-317-9328

View More Info

HMCP015E0

CIRCUIT BREAKER

NSN, MFG P/N

5925013179328

NSN

5925-01-317-9328

MFG

EATON CORPORATION

Description

ACTUATOR FUNCTION: TRIP-RESET
ACTUATOR POSITION DESIGNATION: AT POLE TWO
ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS: 45.0 TO 150.0 AC AND 45.0 TO 150.0 DC ALL LOCATIONS
BODY HEIGHT: 4.062 INCHES NOMINAL
BODY LENGTH: 10.000 INCHES NOMINAL
BODY STYLE: 13B MULTIPOLE-SINGLE ACTUATOR TYPE
BODY WIDTH: 4.125 INCHES NOMINAL
BOSS HEIGHT: 0.125 INCHES NOMINAL
CASE MATERIAL: PLASTIC
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH: 9.000 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH: 1.375 INCHES NOMINAL
CIRCUIT PROTECTION TYPE: OVERCURRENT ALL LOCATIONS
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH: 7.250 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH: 1.375 INCHES NOMINAL
FEATURES PROVIDED: ADJUSTABLE TRIP RELEASE
FREQUENCY IN HERTZ: 50.0 OR 60.0 ALL LOCATIONS
III ARC QUENCHING METHOD: MAGNETIC BLOWOUT
III FRAGILITY FACTOR: MODERATELY RUGGED
III STORAGE TYPE: GENERAL PURPOSE WAREHOUSE
III UNPACKAGED UNIT WEIGHT: 4.500 POUNDS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED: GENERAL PURPOSE
INTERNAL TRIP RELEASE CONFIGURATION: SERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPE: TRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY: 1 TOGGLE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE: 15.0 AMPERES AC AND 15.0 AMPERES DC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS: 25000.0 AC AND 10000.0 DC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY: 4 THREADED HOLE
NOMINAL THREAD SIZE: 0.164 INCHES
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS: 600.0 AC AND 250.0 DC ALL LOCATIONS
POLE QUANTITY: 3
RESET METHOD: MANUAL
TERMINAL TYPE AND QUANTITY: 6 COMPRESSION
THREAD QUANTITY PER INCH: 32
THREAD SERIES DESIGNATOR: UNC
TRIP RELEASE CHARACTERISTIC: INSTANTANEOUS ALL LOCATIONS
TRIP RELEASE METHOD: MAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT: 125.0 ALL LOCATIONS

NZM6B-100/ZM6-80-500-OBI-CNA P -

CIRCUIT BREAKER

NSN, MFG P/N

5925013174328

NSN

5925-01-317-4328

View More Info

NZM6B-100/ZM6-80-500-OBI-CNA P -

CIRCUIT BREAKER

NSN, MFG P/N

5925013174328

NSN

5925-01-317-4328

MFG

KLOCKNER-MOELLER CORP

Description

ACTUATOR FUNCTION: TRIP-RESET
ACTUATOR POSITION DESIGNATION: BETWEEN POLE ONE AND TWO
ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS: 250.0 TO 500.0 AC ALL LOCATIONS
BODY STYLE: 1D RECTANGULAR DIMENSIONAL ENVELOPE
CASE MATERIAL: PLASTIC
CIRCUIT PROTECTION TYPE: UNDERVOLTAGE ALL LOCATIONS
DESIGN CONTROL REFERENCE: NZM6B-100/ZM6-80-500-OBI-CNA P -
EXTRA LONG REFERENCE NUMBER: NZM6B-100/ZM6-80-500-OBI-CNA P VHI002
FEATURES PROVIDED: ADJUSTABLE TRIP RELEASE
FREQUENCY IN HERTZ: 60.0 ALL LOCATIONS
III ARC QUENCHING METHOD: MAGNETIC BLOWOUT
III FRAGILITY FACTOR: MODERATELY RUGGED
III STORAGE TYPE: GENERAL PURPOSE WAREHOUSE
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED: GENERAL PURPOSE
MAIN CONTACT TRIPPING MECHANISM TYPE: TRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY: 1 ROTARY
MANUFACTURERS CODE: 57715
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE: 80.0 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS: 14000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY: 6 TERMINAL
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS: 500.0 AC ALL LOCATIONS
OVERALL HEIGHT: 110.0 MILLIMETERS NOMINAL
OVERALL LENGTH: 210.0 MILLIMETERS NOMINAL
OVERALL WIDTH: 180.0 MILLIMETERS NOMINAL
POLE QUANTITY: 3
REFERENCE NUMBER DIFFERENTIATING CHARACTERISTICS: AS DIFFERENTIATED BY EXTRA LONG REFERENCE NO.
RESET METHOD: MANUAL
TERMINAL TYPE AND QUANTITY: 6 COMPRESSION
THE MANUFACTURERS DATA:
TRIP RELEASE AMBIENT TEMP RATING: 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS
TRIP RELEASE CHARACTERISTIC: INSTANTANEOUS ALL LOCATIONS
TRIP RELEASE METHOD: THERMAL-MAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT: 125.0 ALL LOCATIONS

NZM6B-63/ZM6-6.6-32-OBI-CNA/CL6

CIRCUIT BREAKER

NSN, MFG P/N

5925013174329

NSN

5925-01-317-4329

View More Info

NZM6B-63/ZM6-6.6-32-OBI-CNA/CL6

CIRCUIT BREAKER

NSN, MFG P/N

5925013174329

NSN

5925-01-317-4329

MFG

KLOCKNER-MOELLER CORP

Description

ACTUATOR FUNCTION: TRIP-RESET
ACTUATOR POSITION DESIGNATION: BETWEEN POLE ONE AND TWO
ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS: 16.0 TO 32.0 AC ALL LOCATIONS
BODY STYLE: 1D RECTANGULAR DIMENSIONAL ENVELOPE
CASE MATERIAL: PLASTIC
CIRCUIT PROTECTION TYPE: UNDERVOLTAGE ALL LOCATIONS
FEATURES PROVIDED: ADJUSTABLE TRIP RELEASE AND CURRENT LIMITER
FREQUENCY IN HERTZ: 60.0 ALL LOCATIONS
III ARC QUENCHING METHOD: MAGNETIC BLOWOUT
III FRAGILITY FACTOR: MODERATELY RUGGED
III STORAGE TYPE: GENERAL PURPOSE WAREHOUSE
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED: GENERAL PURPOSE
INTERNAL TRIP RELEASE CONFIGURATION: SERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPE: TRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY: 1 ROTARY
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE: 6.6 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS: 14000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY: 6 TERMINAL
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS: 600.0 AC ALL LOCATIONS
OVERALL HEIGHT: 109.000 MILLIMETERS NOMINAL
OVERALL LENGTH: 133.0 MILLIMETERS NOMINAL
OVERALL WIDTH: 125.0 MILLIMETERS NOMINAL
POLE QUANTITY: 3
RESET METHOD: MANUAL
TERMINAL TYPE AND QUANTITY: 6 COMPRESSION
TRIP RELEASE AMBIENT TEMP RATING: 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS
TRIP RELEASE CHARACTERISTIC: INSTANTANEOUS ALL LOCATIONS
TRIP RELEASE METHOD: THERMAL ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT: 125.0 ALL LOCATIONS

S-4933959-501 RED

RING,INTERRUPT CIRC

NSN, MFG P/N

5925013174993

NSN

5925-01-317-4993

View More Info

S-4933959-501 RED

RING,INTERRUPT CIRC

NSN, MFG P/N

5925013174993

NSN

5925-01-317-4993

MFG

PACO PLASTICS & ENGINEERING INC.

219-3-7906-12

CIRCUIT BREAKER

NSN, MFG P/N

5925013174995

NSN

5925-01-317-4995

View More Info

219-3-7906-12

CIRCUIT BREAKER

NSN, MFG P/N

5925013174995

NSN

5925-01-317-4995

MFG

SENSATA TECHNOLOGIES MARYLAND INC

Description

ACTUATOR FUNCTION: TRIP-RESET
ACTUATOR POSITION DESIGNATION: AT EACH POLE
BODY HEIGHT: 3.359 INCHES NOMINAL
BODY LENGTH: 5.125 INCHES NOMINAL
BODY STYLE: 5C MULTIPOLE-MULTIPLE ACTUATOR TYPE
BODY WIDTH: 3.078 INCHES NOMINAL
BOSS HEIGHT: 0.219 INCHES NOMINAL
CASE MATERIAL: PLASTIC
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH: 3.547 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH: 1.026 INCHES NOMINAL
CIRCUIT PROTECTION TYPE: OVERCURRENT ALL LOCATIONS
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH: 2.750 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH: 1.026 INCHES NOMINAL
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT: ONE, TWO, AND THREE LINKED
FREQUENCY IN HERTZ: 50.0 OR 60.0 ALL LOCATIONS
III FRAGILITY FACTOR: MODERATELY RUGGED
III SPECIAL HANDLING FEATURE: MAGNETIC
III STORAGE TYPE: GENERAL PURPOSE WAREHOUSE
III UNPACKAGED UNIT WEIGHT: 0.200 POUNDS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED: FUNGUS RESISTANT AND MOISTURE RESISTANT
INTERNAL TRIP RELEASE CONFIGURATION: SERIES TRIP W/DUAL RATING FIRST LOCATION SERIES TRIP SECOND LOCATION SERIES TRIP THIRD LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPE: TRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY: 3 TOGGLE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE: 60.0 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS: 5000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY: 6 THREADED HOLE
NOMINAL THREAD SIZE: 0.138 INCHES
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS: 90.0 AC FIRST LOCATION 250.0 AC SECOND LOCATION 250.0 AC THIRD LOCATION
POLE QUANTITY: 3
RESET METHOD: MANUAL
TERMINAL TYPE AND QUANTITY: 9 THREADED STUD
THREAD QUANTITY PER INCH: 32
THREAD SERIES DESIGNATOR: UNC
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT: 2.000 MINIMUM AT 200 PCT AND 10.000 MAXIMUM AT 200 PCT ALL LOCATIONS
TRIP RELEASE CHARACTERISTIC: TIME DELAY ALL LOCATIONS
TRIP RELEASE METHOD: MAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT: 125.0 ALL LOCATIONS

CD3-Z332-1

CIRCUIT BREAKER

NSN, MFG P/N

5925013174995

NSN

5925-01-317-4995

View More Info

CD3-Z332-1

CIRCUIT BREAKER

NSN, MFG P/N

5925013174995

NSN

5925-01-317-4995

MFG

EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV

Description

ACTUATOR FUNCTION: TRIP-RESET
ACTUATOR POSITION DESIGNATION: AT EACH POLE
BODY HEIGHT: 3.359 INCHES NOMINAL
BODY LENGTH: 5.125 INCHES NOMINAL
BODY STYLE: 5C MULTIPOLE-MULTIPLE ACTUATOR TYPE
BODY WIDTH: 3.078 INCHES NOMINAL
BOSS HEIGHT: 0.219 INCHES NOMINAL
CASE MATERIAL: PLASTIC
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH: 3.547 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH: 1.026 INCHES NOMINAL
CIRCUIT PROTECTION TYPE: OVERCURRENT ALL LOCATIONS
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH: 2.750 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH: 1.026 INCHES NOMINAL
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT: ONE, TWO, AND THREE LINKED
FREQUENCY IN HERTZ: 50.0 OR 60.0 ALL LOCATIONS
III FRAGILITY FACTOR: MODERATELY RUGGED
III SPECIAL HANDLING FEATURE: MAGNETIC
III STORAGE TYPE: GENERAL PURPOSE WAREHOUSE
III UNPACKAGED UNIT WEIGHT: 0.200 POUNDS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED: FUNGUS RESISTANT AND MOISTURE RESISTANT
INTERNAL TRIP RELEASE CONFIGURATION: SERIES TRIP W/DUAL RATING FIRST LOCATION SERIES TRIP SECOND LOCATION SERIES TRIP THIRD LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPE: TRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY: 3 TOGGLE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE: 60.0 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS: 5000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY: 6 THREADED HOLE
NOMINAL THREAD SIZE: 0.138 INCHES
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS: 90.0 AC FIRST LOCATION 250.0 AC SECOND LOCATION 250.0 AC THIRD LOCATION
POLE QUANTITY: 3
RESET METHOD: MANUAL
TERMINAL TYPE AND QUANTITY: 9 THREADED STUD
THREAD QUANTITY PER INCH: 32
THREAD SERIES DESIGNATOR: UNC
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT: 2.000 MINIMUM AT 200 PCT AND 10.000 MAXIMUM AT 200 PCT ALL LOCATIONS
TRIP RELEASE CHARACTERISTIC: TIME DELAY ALL LOCATIONS
TRIP RELEASE METHOD: MAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT: 125.0 ALL LOCATIONS

SM-A-973939-12

CIRCUIT BREAKER

NSN, MFG P/N

5925013174995

NSN

5925-01-317-4995

View More Info

SM-A-973939-12

CIRCUIT BREAKER

NSN, MFG P/N

5925013174995

NSN

5925-01-317-4995

MFG

US ARMY COMMUNICATIONS & ELECTRONICS MATERIEL READINESS COMMAND LOGISTICS ENGINEERING DIR

Description

ACTUATOR FUNCTION: TRIP-RESET
ACTUATOR POSITION DESIGNATION: AT EACH POLE
BODY HEIGHT: 3.359 INCHES NOMINAL
BODY LENGTH: 5.125 INCHES NOMINAL
BODY STYLE: 5C MULTIPOLE-MULTIPLE ACTUATOR TYPE
BODY WIDTH: 3.078 INCHES NOMINAL
BOSS HEIGHT: 0.219 INCHES NOMINAL
CASE MATERIAL: PLASTIC
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH: 3.547 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH: 1.026 INCHES NOMINAL
CIRCUIT PROTECTION TYPE: OVERCURRENT ALL LOCATIONS
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH: 2.750 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH: 1.026 INCHES NOMINAL
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT: ONE, TWO, AND THREE LINKED
FREQUENCY IN HERTZ: 50.0 OR 60.0 ALL LOCATIONS
III FRAGILITY FACTOR: MODERATELY RUGGED
III SPECIAL HANDLING FEATURE: MAGNETIC
III STORAGE TYPE: GENERAL PURPOSE WAREHOUSE
III UNPACKAGED UNIT WEIGHT: 0.200 POUNDS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED: FUNGUS RESISTANT AND MOISTURE RESISTANT
INTERNAL TRIP RELEASE CONFIGURATION: SERIES TRIP W/DUAL RATING FIRST LOCATION SERIES TRIP SECOND LOCATION SERIES TRIP THIRD LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPE: TRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY: 3 TOGGLE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE: 60.0 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS: 5000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY: 6 THREADED HOLE
NOMINAL THREAD SIZE: 0.138 INCHES
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS: 90.0 AC FIRST LOCATION 250.0 AC SECOND LOCATION 250.0 AC THIRD LOCATION
POLE QUANTITY: 3
RESET METHOD: MANUAL
TERMINAL TYPE AND QUANTITY: 9 THREADED STUD
THREAD QUANTITY PER INCH: 32
THREAD SERIES DESIGNATOR: UNC
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT: 2.000 MINIMUM AT 200 PCT AND 10.000 MAXIMUM AT 200 PCT ALL LOCATIONS
TRIP RELEASE CHARACTERISTIC: TIME DELAY ALL LOCATIONS
TRIP RELEASE METHOD: MAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT: 125.0 ALL LOCATIONS

APGN-666-1-41-253

CIRCUIT BREAKER

NSN, MFG P/N

5925013175055

NSN

5925-01-317-5055

View More Info

APGN-666-1-41-253

CIRCUIT BREAKER

NSN, MFG P/N

5925013175055

NSN

5925-01-317-5055

MFG

SENSATA TECHNOLOGIES MARYLAND INC

Description

ACTUATOR FUNCTION: TRIP-RESET
ACTUATOR POSITION DESIGNATION: AT POLE TWO
BODY LENGTH: 2.000 INCHES NOMINAL
BODY STYLE: 1B MULTIPOLE-SINGLE ACTUATOR TYPE
BODY WIDTH: 2.250 INCHES NOMINAL
BUSHING LENGTH: 0.625 INCHES NOMINAL
CASE MATERIAL: PLASTIC
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH: 1.530 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH: 0.750 INCHES NOMINAL
CIRCUIT PROTECTION TYPE: OVERCURRENT ALL LOCATIONS
FREQUENCY IN HERTZ: 400.0 ALL LOCATIONS
III ARC QUENCHING METHOD: MAGNETIC BLOWOUT
III FRAGILITY FACTOR: MODERATELY RUGGED
III NONTURN DEVICE DIAMETER: 0.151 INCHES MINIMUM AND 0.161 INCHES MAXIMUM
III NONTURN DEVICE LENGTH: 0.130 INCHES NOMINAL
III NONTURN DEVICE LOCATION: AT 3 OCLOCK AND AT 9 OCLOCK AND AT 12 OCLOCK
III NONTURN DEVICE RADIUS: 0.656 INCHES NOMINAL
III SPECIAL HANDLING FEATURE: MAGNETIC
III STORAGE TYPE: GENERAL PURPOSE WAREHOUSE
III UNPACKAGED UNIT WEIGHT: 9.000 OUNCES
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED: HERMETICALLY SEALED AND SHOCK RESISTANT AND VIBRATION RESISTANT
INTERNAL TRIP RELEASE CONFIGURATION: SERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPE: TRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY: 1 TOGGLE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE: 25.0 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS: 2100.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY: 1 THREADED BUSHING W/PANEL SEAL
MOUNTING SURFACE TO TERMINAL END DISTANCE: 2.232 INCHES MAXIMUM
NOMINAL THREAD SIZE: 0.500 INCHES
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS: 240.0 AC ALL LOCATIONS
POLE QUANTITY: 3
RESET METHOD: MANUAL
TERMINAL TYPE AND QUANTITY: 6 TAB W/SCREW
THREAD PITCH DIAMETERS: 0.4752 TO 0.4787 INCHES
THREAD QUANTITY PER INCH: 32
THREAD SERIES DESIGNATOR: UN
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT: 0.150 MINIMUM AT 200 PCT AND 1.900 MAXIMUM AT 200 PCT ALL LOCATIONS
TRIP RELEASE CHARACTERISTIC: TIME DELAY ALL LOCATIONS
TRIP RELEASE METHOD: MAGNETIC-HYDRAULIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT: 115.0 ALL LOCATIONS

MP1500-052-10

CIRCUIT BREAKER

NSN, MFG P/N

5925013175559

NSN

5925-01-317-5559

View More Info

MP1500-052-10

CIRCUIT BREAKER

NSN, MFG P/N

5925013175559

NSN

5925-01-317-5559

MFG

EATON CORPORATION DBA FLUID POWER DIV DIV POWER AND LOAD MANAGEMENT SYSTEMS USE CAGE CODE 81640 FOR CATALOGING.

Description

BODY LENGTH: 0.250 INCHES NOMINAL
BODY STYLE: 1A SINGLE POLE TYPE
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH: 1.137 INCHES MAXIMUM
III END ITEM IDENTIFICATION: SEA KING HELICOPTER CH124A
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE: 10.0 AMPERES AC AND 10.0 AMPERES DC SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS: 600.0 AC AND 6000.0 DC SINGLE LOCATION
MOUNTING SURFACE TO TERMINAL END DISTANCE: 1.812 INCHES MAXIMUM
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS: 120.0 AC AND 30.0 DC SINGLE LOCATION
POLE QUANTITY: 1
TERMINAL TYPE AND QUANTITY: 2 TAB W/SCREW
THREAD QUANTITY PER INCH: 32
TRIP RELEASE AMBIENT TEMP RATING: 25.0 DEG CELSIUS NOMINAL SINGLE LOCATION

12-12124-08

CIRCUIT BREAKER

NSN, MFG P/N

5925013175560

NSN

5925-01-317-5560

View More Info

12-12124-08

CIRCUIT BREAKER

NSN, MFG P/N

5925013175560

NSN

5925-01-317-5560

MFG

COMPAQ FEDERAL LLC

13225E8129-2

CIRCUIT BREAKER

NSN, MFG P/N

5925013176170

NSN

5925-01-317-6170

View More Info

13225E8129-2

CIRCUIT BREAKER

NSN, MFG P/N

5925013176170

NSN

5925-01-317-6170

MFG

CECOM LR CENTER

Description

ACTUATOR FUNCTION: TRIP-RESET
ACTUATOR POSITION DESIGNATION: AT EACH POLE
BODY LENGTH: 1.985 INCHES MINIMUM AND 2.015 INCHES MAXIMUM
BODY STYLE: 1C MULTIPOLE-MULTIPLE ACTUATOR TYPE
BODY WIDTH: 1.490 INCHES MINIMUM AND 1.510 INCHES MAXIMUM
BUSHING LENGTH: 0.120 INCHES MINIMUM AND 0.140 INCHES MAXIMUM
CASE MATERIAL: PLASTIC
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH: 1.550 INCHES MINIMUM AND 1.570 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH: 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM
CIRCUIT PROTECTION TYPE: OVERCURRENT ALL LOCATIONS
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH: 1.650 INCHES MINIMUM AND 1.670 INCHES MAXIMUM
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH: 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT: ONE AND TWO LINKED
FREQUENCY IN HERTZ: 50.0 OR 60.0 ALL LOCATIONS
III ARC QUENCHING METHOD: MAGNETIC BLOWOUT
III FRAGILITY FACTOR: MODERATELY RUGGED
III STORAGE TYPE: GENERAL PURPOSE WAREHOUSE
III UNPACKAGED UNIT WEIGHT: 5.000 OUNCES
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED: FUNGUS RESISTANT AND MOISTURE RESISTANT
INTERNAL TRIP RELEASE CONFIGURATION: SERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPE: TRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY: 2 TOGGLE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE: 350.0 MILLIAMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS: 1000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY: 4 THREADED HOLE
MOUNTING SURFACE TO TERMINAL END DISTANCE: 1.980 INCHES MAXIMUM
NOMINAL THREAD SIZE: 0.138 INCHES
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS: 250.0 AC ALL LOCATIONS
POLE QUANTITY: 2
RESET METHOD: MANUAL
TERMINAL TYPE AND QUANTITY: 4 QUICK DISCONNECT, MALE
THREAD QUANTITY PER INCH: 32
THREAD SERIES DESIGNATOR: UNC
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT: 2.500 MINIMUM AT 200 PCT AND 20.000 MAXIMUM AT 200 PCT ALL LOCATIONS
TRIP RELEASE CHARACTERISTIC: TIME DELAY ALL LOCATIONS
TRIP RELEASE METHOD: MAGNETIC-HYDRAULIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT: 125.0 ALL LOCATIONS

IUGH11-1-62.350-01

CIRCUIT BREAKER

NSN, MFG P/N

5925013176170

NSN

5925-01-317-6170

View More Info

IUGH11-1-62.350-01

CIRCUIT BREAKER

NSN, MFG P/N

5925013176170

NSN

5925-01-317-6170

MFG

SENSATA TECHNOLOGIES MARYLAND INC

Description

ACTUATOR FUNCTION: TRIP-RESET
ACTUATOR POSITION DESIGNATION: AT EACH POLE
BODY LENGTH: 1.985 INCHES MINIMUM AND 2.015 INCHES MAXIMUM
BODY STYLE: 1C MULTIPOLE-MULTIPLE ACTUATOR TYPE
BODY WIDTH: 1.490 INCHES MINIMUM AND 1.510 INCHES MAXIMUM
BUSHING LENGTH: 0.120 INCHES MINIMUM AND 0.140 INCHES MAXIMUM
CASE MATERIAL: PLASTIC
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH: 1.550 INCHES MINIMUM AND 1.570 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH: 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM
CIRCUIT PROTECTION TYPE: OVERCURRENT ALL LOCATIONS
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH: 1.650 INCHES MINIMUM AND 1.670 INCHES MAXIMUM
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH: 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT: ONE AND TWO LINKED
FREQUENCY IN HERTZ: 50.0 OR 60.0 ALL LOCATIONS
III ARC QUENCHING METHOD: MAGNETIC BLOWOUT
III FRAGILITY FACTOR: MODERATELY RUGGED
III STORAGE TYPE: GENERAL PURPOSE WAREHOUSE
III UNPACKAGED UNIT WEIGHT: 5.000 OUNCES
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED: FUNGUS RESISTANT AND MOISTURE RESISTANT
INTERNAL TRIP RELEASE CONFIGURATION: SERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPE: TRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY: 2 TOGGLE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE: 350.0 MILLIAMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS: 1000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY: 4 THREADED HOLE
MOUNTING SURFACE TO TERMINAL END DISTANCE: 1.980 INCHES MAXIMUM
NOMINAL THREAD SIZE: 0.138 INCHES
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS: 250.0 AC ALL LOCATIONS
POLE QUANTITY: 2
RESET METHOD: MANUAL
TERMINAL TYPE AND QUANTITY: 4 QUICK DISCONNECT, MALE
THREAD QUANTITY PER INCH: 32
THREAD SERIES DESIGNATOR: UNC
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT: 2.500 MINIMUM AT 200 PCT AND 20.000 MAXIMUM AT 200 PCT ALL LOCATIONS
TRIP RELEASE CHARACTERISTIC: TIME DELAY ALL LOCATIONS
TRIP RELEASE METHOD: MAGNETIC-HYDRAULIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT: 125.0 ALL LOCATIONS

JA2S-A3-A-0.35-2

CIRCUIT BREAKER

NSN, MFG P/N

5925013176170

NSN

5925-01-317-6170

View More Info

JA2S-A3-A-0.35-2

CIRCUIT BREAKER

NSN, MFG P/N

5925013176170

NSN

5925-01-317-6170

MFG

EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV

Description

ACTUATOR FUNCTION: TRIP-RESET
ACTUATOR POSITION DESIGNATION: AT EACH POLE
BODY LENGTH: 1.985 INCHES MINIMUM AND 2.015 INCHES MAXIMUM
BODY STYLE: 1C MULTIPOLE-MULTIPLE ACTUATOR TYPE
BODY WIDTH: 1.490 INCHES MINIMUM AND 1.510 INCHES MAXIMUM
BUSHING LENGTH: 0.120 INCHES MINIMUM AND 0.140 INCHES MAXIMUM
CASE MATERIAL: PLASTIC
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH: 1.550 INCHES MINIMUM AND 1.570 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH: 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM
CIRCUIT PROTECTION TYPE: OVERCURRENT ALL LOCATIONS
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH: 1.650 INCHES MINIMUM AND 1.670 INCHES MAXIMUM
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH: 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT: ONE AND TWO LINKED
FREQUENCY IN HERTZ: 50.0 OR 60.0 ALL LOCATIONS
III ARC QUENCHING METHOD: MAGNETIC BLOWOUT
III FRAGILITY FACTOR: MODERATELY RUGGED
III STORAGE TYPE: GENERAL PURPOSE WAREHOUSE
III UNPACKAGED UNIT WEIGHT: 5.000 OUNCES
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED: FUNGUS RESISTANT AND MOISTURE RESISTANT
INTERNAL TRIP RELEASE CONFIGURATION: SERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPE: TRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY: 2 TOGGLE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE: 350.0 MILLIAMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS: 1000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY: 4 THREADED HOLE
MOUNTING SURFACE TO TERMINAL END DISTANCE: 1.980 INCHES MAXIMUM
NOMINAL THREAD SIZE: 0.138 INCHES
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS: 250.0 AC ALL LOCATIONS
POLE QUANTITY: 2
RESET METHOD: MANUAL
TERMINAL TYPE AND QUANTITY: 4 QUICK DISCONNECT, MALE
THREAD QUANTITY PER INCH: 32
THREAD SERIES DESIGNATOR: UNC
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT: 2.500 MINIMUM AT 200 PCT AND 20.000 MAXIMUM AT 200 PCT ALL LOCATIONS
TRIP RELEASE CHARACTERISTIC: TIME DELAY ALL LOCATIONS
TRIP RELEASE METHOD: MAGNETIC-HYDRAULIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT: 125.0 ALL LOCATIONS

Q0M100L

CIRCUIT BREAKER

NSN, MFG P/N

5925013176721

NSN

5925-01-317-6721

View More Info

Q0M100L

CIRCUIT BREAKER

NSN, MFG P/N

5925013176721

NSN

5925-01-317-6721

MFG

SCHNEIDER ELECTRIC USA INC.

Description

ACTUATOR POSITION DESIGNATION: BETWEEN POLE ONE AND TWO
BODY HEIGHT: 38.0 MILLIMETERS NOMINAL
BODY LENGTH: 59.0 MILLIMETERS NOMINAL
BODY STYLE: 9B MULTIPOLE-SINGLE ACTUATOR TYPE
BODY WIDTH: 76.0 MILLIMETERS NOMINAL
CASE MATERIAL: PLASTIC
CIRCUIT PROTECTION TYPE: OVERCURRENT FIRST LOCATION
FREQUENCY IN HERTZ: 60.0 ALL LOCATIONS
III END ITEM IDENTIFICATION: CFSS DEPOT STOCK
MANUAL ACTUATOR TYPE AND QUANTITY: 1 TOGGLE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE: 100.0 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS: 10000.0 AC ALL LOCATIONS
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS: 120.000 AC AND 240.0 AC ALL LOCATIONS
POLE QUANTITY: 2
TERMINAL TYPE AND QUANTITY: 2 SCREW

590-422-7

CIRCUIT BREAKER

NSN, MFG P/N

5925013178441

NSN

5925-01-317-8441

View More Info

590-422-7

CIRCUIT BREAKER

NSN, MFG P/N

5925013178441

NSN

5925-01-317-8441

MFG

BUFFALO SUPPLY INC

Description

DESIGN CONTROL REFERENCE: 590-422-7
MANUFACTURERS CODE: 1CH83
SPECIAL FEATURES: FOR USE ON IRRIGATOR,SURGICAL; MDL. 203-150 ORTHOTEC; NSN 6530-01-314-1228
THE MANUFACTURERS DATA:

CD3-C3-A-50-240-3

CIRCUIT BREAKER

NSN, MFG P/N

5925013179323

NSN

5925-01-317-9323

View More Info

CD3-C3-A-50-240-3

CIRCUIT BREAKER

NSN, MFG P/N

5925013179323

NSN

5925-01-317-9323

MFG

EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV

Description

ACTUATOR FUNCTION: TRIP-RESET
ACTUATOR POSITION DESIGNATION: AT EACH POLE
BODY LENGTH: 5.790 INCHES MINIMUM AND 5.810 INCHES MAXIMUM
BODY STYLE: 8C MULTIPOLE-MULTIPLE ACTUATOR TYPE
BODY WIDTH: 3.108 INCHES MAXIMUM
BOSS HEIGHT: 0.209 INCHES MINIMUM AND 0.229 INCHES MAXIMUM
CASE MATERIAL: PLASTIC
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH: 3.537 INCHES MINIMUM AND 3.557 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH: 1.016 INCHES MINIMUM AND 1.036 INCHES MAXIMUM
CIRCUIT PROTECTION TYPE: OVERCURRENT ALL LOCATIONS
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH: 2.740 INCHES MINIMUM AND 2.760 INCHES MAXIMUM
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH: 1.016 INCHES MINIMUM AND 1.036 INCHES MAXIMUM
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT: ONE, TWO, AND THREE LINKED
FREQUENCY IN HERTZ: 400.0 ALL LOCATIONS
III ARC QUENCHING METHOD: MAGNETIC BLOWOUT
III FRAGILITY FACTOR: MODERATELY RUGGED
III STORAGE TYPE: GENERAL PURPOSE WAREHOUSE
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED: DUSTPROOF AND FUNGUS RESISTANT
INTERNAL TRIP RELEASE CONFIGURATION: SERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPE: TRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY: 3 TOGGLE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE: 50.0 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS: 2000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY: 6 THREADED HOLE
MOUNTING SURFACE TO TERMINAL END DISTANCE: 2.599 INCHES MINIMUM AND 2.619 INCHES MAXIMUM
NOMINAL THREAD SIZE: 0.138 INCHES
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS: 240.0 AC ALL LOCATIONS
POLE QUANTITY: 3
RESET METHOD: MANUAL
TERMINAL TYPE AND QUANTITY: 6 THREADED STUD
THREAD QUANTITY PER INCH: 32
THREAD SERIES DESIGNATOR: UNC
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT: 0.280 MINIMUM AT 200 PCT AND 1.000 MAXIMUM AT 200 PCT ALL LOCATIONS
TRIP RELEASE CHARACTERISTIC: TIME DELAY ALL LOCATIONS
TRIP RELEASE METHOD: MAGNETIC-HYDRAULIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT: 150.0 ALL LOCATIONS

CD3-C3-DU-30-240-3

CIRCUIT BREAKER

NSN, MFG P/N

5925013179324

NSN

5925-01-317-9324

View More Info

CD3-C3-DU-30-240-3

CIRCUIT BREAKER

NSN, MFG P/N

5925013179324

NSN

5925-01-317-9324

MFG

EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV

Description

ACTUATOR FUNCTION: TRIP-RESET
ACTUATOR POSITION DESIGNATION: AT EACH POLE
BODY LENGTH: 5.790 INCHES MINIMUM AND 5.810 INCHES MAXIMUM
BODY STYLE: 8C MULTIPOLE-MULTIPLE ACTUATOR TYPE
BODY WIDTH: 3.108 INCHES MAXIMUM
BOSS HEIGHT: 0.209 INCHES MINIMUM AND 0.229 INCHES MAXIMUM
CASE MATERIAL: PLASTIC
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH: 3.537 INCHES MINIMUM AND 3.557 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH: 1.016 INCHES MINIMUM AND 1.036 INCHES MAXIMUM
CIRCUIT PROTECTION TYPE: OVERCURRENT ALL LOCATIONS
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH: 2.740 INCHES MINIMUM AND 2.760 INCHES MAXIMUM
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH: 1.016 INCHES MINIMUM AND 1.036 INCHES MAXIMUM
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT: ONE, TWO, AND THREE LINKED
FREQUENCY IN HERTZ: 400.0 ALL LOCATIONS
III ARC QUENCHING METHOD: MAGNETIC BLOWOUT
III FRAGILITY FACTOR: MODERATELY RUGGED
III STORAGE TYPE: GENERAL PURPOSE WAREHOUSE
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED: DUSTPROOF AND FUNGUS RESISTANT
INTERNAL TRIP RELEASE CONFIGURATION: SERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPE: TRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY: 3 TOGGLE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE: 30.0 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS: 2000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY: 6 THREADED HOLE
MOUNTING SURFACE TO TERMINAL END DISTANCE: 2.599 INCHES MINIMUM AND 2.619 INCHES MAXIMUM
NOMINAL THREAD SIZE: 0.138 INCHES
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS: 240.0 AC ALL LOCATIONS
POLE QUANTITY: 3
RESET METHOD: MANUAL
TERMINAL TYPE AND QUANTITY: 6 THREADED STUD
THREAD QUANTITY PER INCH: 32
THREAD SERIES DESIGNATOR: UNC
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT: 0.280 MINIMUM AT 200 PCT AND 1.000 MAXIMUM AT 200 PCT ALL LOCATIONS
TRIP RELEASE CHARACTERISTIC: TIME DELAY ALL LOCATIONS
TRIP RELEASE METHOD: MAGNETIC-HYDRAULIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT: 150.0 ALL LOCATIONS

TEC36150

CIRCUIT BREAKER

NSN, MFG P/N

5925013179325

NSN

5925-01-317-9325

View More Info

TEC36150

CIRCUIT BREAKER

NSN, MFG P/N

5925013179325

NSN

5925-01-317-9325

MFG

GENERAL ELECTRIC CO ELECTRICAL DISTRIBUTION AND CONTROL

Description

ACTUATOR FUNCTION: TRIP-RESET
ACTUATOR POSITION DESIGNATION: AT POLE TWO
ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS: 600.0 TO 2700.0 AC ALL LOCATIONS
BODY HEIGHT: 3.375 INCHES NOMINAL
BODY LENGTH: 8.187 INCHES NOMINAL
BODY STYLE: 11B MULTIPOLE-SINGLE ACTUATOR TYPE
BODY WIDTH: 4.125 INCHES NOMINAL
BOSS HEIGHT: 0.125 INCHES NOMINAL
CASE MATERIAL: PLASTIC
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH: 4.874 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH: 0.687 INCHES NOMINAL
CIRCUIT PROTECTION TYPE: OVERCURRENT ALL LOCATIONS
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH: 4.874 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH: 1.375 INCHES NOMINAL
FEATURES PROVIDED: ADJUSTABLE TRIP RELEASE
FREQUENCY IN HERTZ: 60.0 ALL LOCATIONS
III ARC QUENCHING METHOD: MAGNETIC BLOWOUT
III FRAGILITY FACTOR: MODERATELY RUGGED
III STORAGE TYPE: GENERAL PURPOSE WAREHOUSE
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED: DUSTPROOF
INTERNAL TRIP RELEASE CONFIGURATION: SERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPE: TRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY: 1 TOGGLE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE: 150.0 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS: 25000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY: 4 UNTHREADED HOLE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS: 600.0 AC ALL LOCATIONS
POLE QUANTITY: 3
RESET METHOD: MANUAL
TERMINAL TYPE AND QUANTITY: 6 COMPRESSION
TRIP RELEASE CHARACTERISTIC: INSTANTANEOUS ALL LOCATIONS
TRIP RELEASE METHOD: MAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT: 125.0 ALL LOCATIONS
UNTHREADED MOUNTING HOLE DIAMETER: 0.196 INCHES NOMINAL

TJK436175

CIRCUIT BREAKER

NSN, MFG P/N

5925013179326

NSN

5925-01-317-9326

View More Info

TJK436175

CIRCUIT BREAKER

NSN, MFG P/N

5925013179326

NSN

5925-01-317-9326

MFG

GENERAL ELECTRIC CO ELECTRICAL DISTRIBUTION AND CONTROL

Description

ACTUATOR FUNCTION: TRIP-RESET
ACTUATOR POSITION DESIGNATION: AT POLE TWO
ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS: 525.0 TO 1750.0 AC ALL LOCATIONS
BODY HEIGHT: 3.187 INCHES NOMINAL
BODY LENGTH: 10.125 INCHES NOMINAL
BODY STYLE: 11B MULTIPOLE-SINGLE ACTUATOR TYPE
BODY WIDTH: 8.125 INCHES NOMINAL
BOSS HEIGHT: 0.125 INCHES NOMINAL
CASE MATERIAL: PLASTIC
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH: 7.624 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH: 1.375 INCHES NOMINAL
CIRCUIT PROTECTION TYPE: OVERCURRENT ALL LOCATIONS
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH: 7.624 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH: 2.750 INCHES NOMINAL
FEATURES PROVIDED: ADJUSTABLE TRIP RELEASE
FREQUENCY IN HERTZ: 60.0 ALL LOCATIONS
III ARC QUENCHING METHOD: MAGNETIC BLOWOUT
III FRAGILITY FACTOR: MODERATELY RUGGED
III STORAGE TYPE: GENERAL PURPOSE WAREHOUSE
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED: DUSTPROOF
MAIN CONTACT TRIPPING MECHANISM TYPE: TRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY: 1 TOGGLE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE: 175.0 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS: 22000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY: 6 UNTHREADED HOLE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS: 600.0 AC ALL LOCATIONS
POLE QUANTITY: 3
RESET METHOD: MANUAL
TERMINAL TYPE AND QUANTITY: 6 COMPRESSION
TRIP RELEASE AMBIENT TEMP RATING: 25.0 DEG CELSIUS NOMINAL ALL LOCATIONS
TRIP RELEASE CHARACTERISTIC: INSTANTANEOUS ALL LOCATIONS
TRIP RELEASE METHOD: THERMAL-MAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT: 125.0 ALL LOCATIONS
UNTHREADED MOUNTING HOLE DIAMETER: 0.196 INCHES NOMINAL

HMCP150T4

CIRCUIT BREAKER

NSN, MFG P/N

5925013179327

NSN

5925-01-317-9327

View More Info

HMCP150T4

CIRCUIT BREAKER

NSN, MFG P/N

5925013179327

NSN

5925-01-317-9327

MFG

EATON CORPORATION

Description

ACTUATOR FUNCTION: TRIP-RESET
ACTUATOR POSITION DESIGNATION: AT POLE TWO
ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS: 450.0 TO 1500.0 AC AND 450.0 TO 1500.0 DC ALL LOCATIONS
BODY HEIGHT: 3.500 INCHES NOMINAL
BODY LENGTH: 6.000 INCHES NOMINAL
BODY STYLE: 11B MULTIPOLE-SINGLE ACTUATOR TYPE
BODY WIDTH: 4.125 INCHES NOMINAL
BOSS HEIGHT: 0.125 INCHES NOMINAL
CASE MATERIAL: PLASTIC
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH: 4.500 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH: 1.375 INCHES NOMINAL
CIRCUIT PROTECTION TYPE: OVERCURRENT ALL LOCATIONS
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH: 4.500 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH: 1.375 INCHES NOMINAL
FEATURES PROVIDED: ADJUSTABLE TRIP RELEASE
FREQUENCY IN HERTZ: 50.0 OR 60.0 ALL LOCATIONS
III ARC QUENCHING METHOD: MAGNETIC BLOWOUT
III FRAGILITY FACTOR: MODERATELY RUGGED
III PACKAGED UNIT WEIGHT: 4.500 POUNDS
III STORAGE TYPE: GENERAL PURPOSE WAREHOUSE
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED: GENERAL PURPOSE
INTERNAL TRIP RELEASE CONFIGURATION: SERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPE: TRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY: 1 TOGGLE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE: 150.0 AMPERES AC AND 150.0 AMPERES DC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS: 25000.0 AC AND 10000.0 DC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY: 4 THREADED HOLE
NOMINAL THREAD SIZE: 0.164 INCHES
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS: 600.0 AC AND 250.0 DC ALL LOCATIONS
POLE QUANTITY: 3
RESET METHOD: MANUAL
TERMINAL TYPE AND QUANTITY: 1 COMPRESSION
THREAD QUANTITY PER INCH: 32
THREAD SERIES DESIGNATOR: UNC
TRIP RELEASE CHARACTERISTIC: INSTANTANEOUS ALL LOCATIONS
TRIP RELEASE METHOD: MAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT: 150.0 ALL LOCATIONS